(11) A booster pump within the premise plumbing of a building or on the service lateral connection, including a home booster pump, is acceptable if:(a) the pump is not necessary to resolve deficiencies related to the necessary minimum pressures at the point of connection for the service lateral per Section R309-105-9;(b) the PWS approves the pump installation; and
(c) the pump installation and operation meet the applicable requirements in the International Plumbing Code and any amendments that the Department of Commerce has adopted.
R309-540-7. Pump Appurtenances.
(1) Valves.
(a) Valves shall be provided to allow satisfactory operation and maintenance of a pump facility.
(b) Each pump shall have an isolation valve:
(i) on the intake side of the pump; and
(ii) on the discharge side of the pump.
(c) An air release valve shall:
(i) be provided where needed to allow the release of accumulated air in pump facility piping; and
(ii) meet the requirements of Subsection R309-550-6(6).
(d) If used, a foot valve shall be sized according to the manufacturer's recommendation.
(2) Piping. Piping for a pump shall:
(a) have watertight joints; and
(b) be protected against surge or water hammer
(3) Controls. Controls for a pump shall:
(a) be protected from flooding;
(b) allow a pump motor to operate at rated capacity without overloading;
(c) have proper overload protection for the air temperature encountered;
(d) provide for alternate operation of pumps where two or more pumps are installed;
(e) prevent the pump motor from starting during pump backspin;
(f) set start and cutoff pressures to prevent continuous on-off cycling;
(g) follow manufacturer's requirements for automatic cutoff pressure; and
(h) prevent surge pressures from activating controls that turn on pumps or other equipment outside the normal design cycle of operation.
(4) Water Pre-Lubrication of Pump Bearings. If water is used for automatic pre-lubrication of pump bearings, and an auxiliary direct-drive power supply is provided:
(a) the pre-lubrication line shall have a valved bypass around the automatic control so that the bearings can be lubricated manually before the pump is started; or
(b) the pre-lubrication controls shall be wired to the auxiliary power supply.
(5) Pressure Measurement. A pump or group of pumps operating together shall have a means of measuring pressure:
(a) on the discharge line; and
(b) on the intake line capable of indicating positive and negative pressure.
(6) Standby Power Supply.
(a) A community water system that relies solely on a pump facility to supply water to a service area shall be provided with standby power, power using a permanent or portable generator or electrical service from two independent substations.
(b) If a fuel-operated generator provides standby power:
(i) the water supply shall be protected from contamination from the fuel supply and fuel line; and
(ii) a carbon monoxide detector shall be installed if the generator is located indoors.
R309-540-8. Hydropneumatic Facilities.
(1) Section R309-540-8 applies to air-over-water, diaphragm, and bladder hydropneumatic pressure tanks.
(2) Section R309-540-8 does not apply to:
(a) a surge protection tank;
(b) pressure relief equipment; or
(c) a pressure tank dedicated solely to fire suppression.
(3) Where a hydropneumatic facility is the only means available for a PWS to meet the minimum distribution system pressure requirements of Section R309-105-9, the number of pumps shall meet the requirements in Subsection R309-540-6(2).
(4) A hydropneumatic pressure tank shall have:
(a) NSF/ANSI 61 certification; and
(b) ASME Boiler and Pressure Vessel Code certification.
(5) A community water system may not use the volume of a hydropneumatic pressure tank to meet the water storage sizing requirements in Section R309-510-8.
(6) A below-ground location for a hydropneumatic pressure tank and appurtenances shall meet the requirements of:
(a) Subsection R309-540-5(2) for flood protection and site drainage;
(b) Subsection R309-540-5(4) for pump station drainage and flooding prohibition;
(c) Subsection R309-540-5(5) for access; and