(5) Every reproduction of the Seal of Registration and every letter and number placed thereon, shall be of sufficient size to render such seal, letter, and number distinct and clearly legible.R710-5-7. Amendments and Additions.
(1) At the time of service, all servicing shall be done in accordance with the adopted NFPA standard, adopted statutes, and these rules.
(2) NFPA 25, Chapter 5, Section 5.1, Table 5.1 is amended as follows: On line 16 of the "Inspection" section, the "Obstruction Reference" is changed from 14.2.2 to 14.2.1.
(3) NFPA 25, Chapter 5, Section 5.1, Table 5.1 is amended as follows: On line one of the "Investigation" section, the "Obstruction Reference" is changed from 14.2.1 to 14.2.2.
(4) Frequency and Labels.
(a) Automatic fire sprinkler systems, standpipes, and fire pumps shall be inspected annually by a person holding a certificate of registration as required in Section 3.1 of these rules.
(b) Automatic fire sprinkler systems that pass the three-year and five-year inspection requirements as required in NFPA 25, Tables 5.1 and 13.1, shall have a label affixed to the riser indicating the specific inspection or inspections that was completed, the month and year those inspections was performed, the person who performed the inspection, and the person performing the inspections certificate of registration number.
(c) The label shall be affixed to the riser using a heatless process, shall be 3 in. X 5 in., shall have the official seal of registration of the SFM affixed to the label, shall be constructed of durable material, and shall be the self-destructive type when removal is attempted.
(5) Accepted Inspection Forms.
(a) Inspection forms listed in NFPA 25, Annex B, Section B.2, shall be used as the accepted inspection forms.
(b) Inspection form format shall be as required in NFPA 25, Annex B, Section B.1(4).
(c) A similar equivalent inspection form approved by the SFM may be used as the accepted forms for inspection, testing, and maintenance of water-based fire protection systems.
(d) A copy of the completed inspection forms shall be left in a water proof container affixed to the riser.
(6) Newly installed automatic fire sprinkler systems, standpipes, and fire pumps are exempt from the annual testing requirement required in Section 6.2 of these rules, for one year from the approval date of the initial installation acceptance testing.
R710-5-8. Adjudicative Proceedings.
(1) All adjudicative proceedings performed by the agency shall proceed informally as authorized by Sections 63G-4-202 and 63G-4-203.
(2) The issuance, renewal, or continued validity of a certificate of registration may be denied, suspended, or revoked, if the SFM finds that the applicant or the person has committed any of the following violations:
(a) the applicant or person is not the real person in interest;
(b) the applicant or person provides material misrepresentation or false statements on the application;
(c) the applicant or person refuses to allow inspection by the SFM, or his duly authorized deputies;
(d) the applicant or person for a certificate of registration does not have the proper equipment to conduct the operations for which application is made;
(e) the applicant or person for a certificate of registration does not possess the qualifications of skill or competence to conduct the operations for which application is made, as evidenced by failure to pass the examination pursuant to Section 3.3 of these rules;
(f) the applicant or person refuses to take the examination required by Section 3.3 of these rules;
(g) the applicant or person fails to pay the certification of registration, examination or other required fees as required in Section 8 of these rules;
(h) the applicant or person has been convicted of one or more federal, state or local laws;
(i) the applicant or person has been convicted of a violation of the adopted rules or been found by a board administrative proceeding to have violated the adopted rules;
(j) any offense or finding of unlawful conduct, or there is or may be, a threat to the public's health or safety if the applicant or person were granted a certificate of registration; or
(k) there are other factors upon which a reasonable and prudent person would rely to determine the suitability of the applicant or person to safely and competently engage in the practice of servicing fire sprinkler system equipment.
(3) A person whose certificate of registration is suspended or revoked by the SFM shall have an opportunity for a hearing before the board if requested by that person within 20 days after receiving notice.
(4) All adjudicative proceedings, other than criminal prosecution, taken by the SFM to enforce the Utah Fire Prevention and Safety Act, and these rules, shall commence in accordance with Section 63G-4-201.
(5) The board shall act as the hearing authority, and shall convene after timely notice to all parties involved. The board shall be the final authority on the suspension or revocation of a certificate of registration.
(6) The board shall direct the SFM to issue a signed order to the parties involved giving the decision of the board within a reasonable time of the hearing pursuant to Section 63G-4-203.