(1) Except for Subsection (2), the manager shall ensure that a pool constructed after September 16, 1996, is not used for night swimming without underwater lighting.(2) A pool does not need to meet the lighting requirement described in Subsection (1) if the manager can demonstrate to the local health officer that a six-inch diameter black disk on a white background placed in the deepest part of the pool can be clearly observed from the pool deck during nighttime hours, which are 30 minutes before sunset to 30 minutes after sunrise.
(3) Where night swimming is permitted and underwater lighting is used, the manager shall ensure that:
(a) artificial lighting is provided so that each area of the pool, including the deepest portion, is visible from the edge of the pool deck;
(b) area lighting is provided for the pool deck at not less than ten horizontal foot-candles, ten lumens per square foot, or 108 lux that is directed away from the pool surface as is practical to reduce glare;
(c) for outdoor pools, any combination of overhead and underwater lighting provides maintained illumination not less than ten horizontal foot-candles, ten lumens per square foot, or 108 lux at the pool water surface; and
(d) for indoor pools, any combination of overhead and underwater lighting provides maintained illumination of not less than 30 horizontal foot-candles, 30 lumens per square foot, or 323 lux at the pool water surface.
(4) The manager shall ensure that electrical wiring conforms with Article 680 of the NFPA 70, NEC, 2023 Edition, incorporated by reference in this rule.
(5) The manager shall ensure that any facility with an indoor pool, pool equipment room, access space, dressing room, shower room, and toilet space is ventilated in accordance with the American Society of Heating, Refrigerating and Air-Conditioning Engineers Standard 62.1-2016, incorporated by reference in this rule.
R392-302-19. Circulation Systems.
(1) The manager shall ensure that:
(a) each individual pool has an independent circulation system that is in continuous operation;
(b) when the pool is open for bathing, the normal waterline of the pool is maintained to promote continuous skimming for any surge condition;
(c) when an overflow gutter system is used, the water is maintained at the overflow rim of the gutter;
(d) when a skimmer is used, the water is maintained at the midpoint of the skimmer opening;
(e) the circulation system meets the minimum turnover time listed in Table 1;
(f) if a single pool circulation system incorporates more than one of the pool types listed in Table 1:
(i) the entire pool circulation system is designed with the shortest turnover rate required in Table 1 for the incorporated pool types; or
(ii) the pool circulation system is designed with multiple circulation zones that each meet the recirculation flow rate required in Table 1;
(g) the circulation equipment is operated continuously except for any period of maintenance;
(h) a rate of flow indicator, reading in gallons per minute, is:
(i) functioning; and
(ii) properly installed:
(A) according to manufacturer recommendations; and
(B) in a place and position where authorized personnel can easily read the indicator;
(i) the pump room, or the area housing the circulation equipment, is:
(i) designed and maintained:
(A) according to manufacturer recommendations; and
(B) with adequate working space for equipment maintenance, including disassembly, removal, and replacement;
(ii) protected from environmental conditions, including UV radiation; and
(iii) secured from unauthorized personnel;
(j) at least one valve:
(i) regulates the control of water flow in the system of circulation pipes; and
(ii) is located to be easily accessible for maintenance or replacement;
(k) written operational instructions for circulation equipment are made available upon request;
(l) circulation equipment, including multiport valves, if used, comply with NSF/ANSI/CAN 50 - 2021 Equipment and Chemicals for Swimming Pools, Spas, Hot Tubs, and Other Recreational Water Facilities, incorporated by reference in this rule; and
(m) each pump or series of pumps used for pool water circulation under normal operating conditions:
(i) has adequate capacity to provide the minimum turnover rate specified in Table 1;
(ii) can provide flow adequate for the backwashing of filters; and
(iii) can maintain the required minimum circulation flow rate at a dynamic head that includes, in addition to fitting and friction losses:
(A) except as described in Subsection (10), an additional 15 feet of head for pool inlet orifices; and
(B)(aa) an additional 15 feet of head for rapid sand filters, vacuum precoat media filters, or vacuum cartridge filters; or
(bb) an additional 40 feet of head for pressure precoat media filters, high-rate sand filters, or cartridge filters.
(2) A variable speed pump is permitted for pool water circulation if the manager ensures that: